Hi,
We use 2878696 IL MOD BK DI8 DO4-PAC modbus copuler with these components at this order:<pre>
1- 2878696 IL MOD BK DI8 DO4-PAC
2- 2878447 IB IL AI 4/EF-PAC
3- 2861302 IB IL AI 2/SF-PAC
4- 2861302 IB IL AI 2/SF-PAC
5- 2861315 IB IL AO 1/SF-PAC
6- 2861315 IB IL AO 1/SF-PAC</pre>
We can read first 8 AI values from the module with these registers (40194 40195......40201).
But we can not drive 5th and 6th modules with the registers 40580 and 40581.
Our control system is Schneider's Foxboro I/A system (V8.2) and our Modbus module is FBM230.
When we create a block (IOUT block) it gives an error at 40580 or 40581. Also we tried 40582, 40583 etc...We have no solution.
Could you help me about this problem?