Voltage Problem 3 Phase Generator

T

Thread Starter

Tom kinczel

I have a 3 phase 125KW generator with a selector switch for 3 voltage settings 120/240 single phase, 120/208 3 phase, and 277/480 3 phase. Every time I switch the selector switch between voltages, I have to adjust the voltage using the adjustment on the voltage regulator. I changed the voltage regulator but have the same problem. Any idea what it could be.

[email protected]
 
Tom kinczel,

Previously, did you not have to manually adjust voltage when switching voltage outputs?

When did this problem start?

Can you provide any information about the generator and AVR (manufacturer, model number, etc.)?
 
i am not switching voltage, just turning it on with the regulator switch, started a month ago, i only use this two days a week when i am crushing ore., the voltage is good untill it cuts out or spikes to 350
marathon electric brushless alternator, 680x
 