Indusoft AS511 driver

V

Thread Starter

vlad

Has anyone configured Indusoft's AS511 driver? I should connect an old S5 PLC to Indusoft based HMI. After system rebooting, when I first click Run, receive: "Error initializing driver AS511 11.04: Invalid serial port". Second:"Port allredy in use".
Nbr of port is correct, I checked up it many times.

Any suggestion?
 
A

Andre Bastos

Hi,
You can workaround this issue following the steps below:
- Stop your InduSoft Web Studio runtime, if it is running
- On your application, go to the COMM tab
- find the Drivers->AS511 folder
- right-click on the AS511 and select "Settings"
- in the "Order Of Words" field, please type "0"

It should solve the problem.
We are about to release a newer driver version that takes care of this issue, and should be able to download from www.indusoft.com shortly.
Should you have any question, please let me know.
Andre
 
T

Thomas Richards

I've been having a similar driver issue when trying to connect my Velocio PLC to my PC's InTouch Machine Edition. I've been using the MODBUS Protocol RTU abbreviated MODBU. Whenever I try to run the application and retrieve a tag from its MODBUS address, I get the same "Error Initializing MODBU Driver: Invalid Serial Port." I've checked to make sure that the serial ports match and even tried changing them to no avail. When I sent my application to a different computer, it worked without an issue. Any ideas?

Thanks so much
 