Forced Signals on Tristation

D

Thread Starter

Diaa

To tristation experts, Is there a function block or a method to automatically collect all overridden signals in one page?
 
In Tristation from the Control Panel:
Controller tree > Controller Panel > Commands menu
choose the "List Disabled Points" Command

It will list all the disabled points.

The Tricon function block SYS_MP_EXT_STATUS has a POINTS_DISABLED parameter that can be used to display the number of points disabled and create an alarm if any points are disabled.

> To tristation experts, Is there a function block or a
> method to automatically collect all overridden signals in
> one page?
 
Top