Instrumentation and Process Control

Liquid Level Measurements


11 questions

Page 2 of M03d478b72a271d2b450124b08e12daad2 0 of 11 answers revealed (0%)
  • Question 1 of 11

    A vessel containing a weak acid/water mixture has a calibrated level range of 0 to 10 feet, measured by a pressure transmitter at the bottom. Suppose that the specific gravity of the normal mixture is 1.12 (112% of the density of water).

    Now, suppose some pure acid is added to the vessel, increasing the actual liquid level and increasing the liquid density at the same time. The new liquid level is 7 feet high and the specific gravity has increased to 1.35. Assuming the transmitter has been calibrated for the original specific gravity of 1.12, what will its output signal correspond to in feet of liquid level? In other words, if this transmitter’s output signal were driving a level indicator device for an operator to read, how many feet of level would the indicator device register?

    Identify an alternative method for liquid level measurement that would not be affected by changes in liquid density.

    Reveal answer
  • Question 2 of 11

    An open vessel contains water at 60°F. A pressure transmitter located at the bottom of the vessel measures the hydrostatic pressure (“head”) generated by the water and outputs a signal corresponding to level.

    Suppose that the temperature of this vessel were to increase over time to 110°F due to exposure to very hot outside air (the vessel is located in Death Valley, California during the summer).

    Knowing that an increase in water temperature will result in a decrease in density, what will happen to the level transmitter’s output as the vessel heats up? Will the transmitter output increase, decrease, or stay the same? Why?

    Assume that no water enters or exits the vessel during the period of heating from 60°F to 110°F.

    Reveal answer
  • Question 3 of 11

    A vessel holding some process liquid needs to have its level monitored. The range of level in this vessel is 0 to 20 feet, and the process liquid has a specific gravity of 1.0 (like water). Someone decides to attach a pressure transmitter to the bottom of the vessel to infer level from hydrostatic pressure like this:

    Later, a top is added to this vessel to keep rain from entering in. Unfortunately, though, this process liquid tends to emit vapor which will be trapped by the closed vessel and create a pressure inside of it. A small vent is added to the top of the vessel to permit the vapor to escape, but it is a small vent, not big enough to ensure a total absence of vapor pressure buildup at all times:

    What problem in level measurement will result from there being an occasional vapor pressure buildup inside this vessel? How may this problem be corrected so that the liquid level will be accurately measured at all times?

    Reveal answer